Skip links

Filling the Gap in the Market to Provide Reliable, Cost Effective, Stand-Alone Automatic Fire Suppression Systems.

AutoFireX® DHP - Direct High-Pressure Co2 Systems

These are primarily a Pre-Engineered Automatic Fire detection and suppression System utilising High pressure agent Co2. These Units are designed, manufactured, and tested in ISO 9001:2015 certified facilities.

MANUFACTURING & PROCESS APPLICATIONS

Direct High Pressure Systems Protects

ELECTRICAL CABINETS & SERVER RACKS

LT & HT Switchgear Panels, Capacitor Panels, Server racks in Data Centres, PLC & process automation control cabinets; critical data processing equipment; UPS cabinets; medical equipment; switchgears, HVAC Panels, Escalator Panels, Telecom towers

Direct High Pressure Systems

The AutoFireX® Linear Pneumatic Fire Detection Tubing (FDT) is installed and connected to DHP Valve and routed throughout the protected hazard area/enclosure. Being heat sensitive, the primary function of Linear Pneumatic Fire Detection Tube (under pressure) is to detect heat/fire and activate the valve for discharge of the agent by rupturing at the hottest point along its installed length on flame impingement. On rupture a nozzle is formed at the burst point.

The Co2 clean agent under pressure, in the cylinder then flows out through the burst point, distributing the Co2 gas through the protected enclosure and extinguishing the fire instantly.

Each DHP system consists of a High-Grade Brass Direct valve assembly with 3 Ports (1 x Inlet connection-W28.8x1/14"- 1 1/8"-12 UNF-2A, M 25x 2; 1 x Outlet connection M10x0,75 & 1 x Filling connection- W 21,8 x 1/14") and siphon tube, a quarter turn Next Gen isolation valve with a G 1/8” threaded push-in/ slip on union is provided to connect the AutoFireX® Fire Detection Tubing. A Pressure gauge is also be provided to monitor the system pressure. The system is supplied complete with light weight UL approved High-Pressure Seam less Aluminium Alloy Cylinders and Brackets and DHP valve Guard.

To assist in annunciation, an optional pressure switch can be installed at the end of the detection line using an End of Line Adaptor, also available with the system. The pressure switch provides a potential free contact, that can be interfaced, with existing FACP (Fire Alarm Control Panel) to indicate system discharge, shutdown ventilation, shut-off electrical power, as may be required. Alternatively, it can also be connected to a Audio Visual (A/V) alarm unit for annunciation.

Since the units are supplied as automatic units no simultaneous manual or electric actuators are provided.

PRODUCT CODEAGENT QTY.CYLINDER VOLUMEOPERATING PRESSURE(@21oC)MAX VOLUME COVERAGE*
40001011 kg1400 ml15 Bar1.0-1.10m3

*Figures based on ideal conditions in fully enclosed space. Actual figures may vary according to application.

Maximum volume coverage is determined by agent concentration discharged within the enclosure where the fire hazard is located. The discharge time for DHP system utilising various agents differ from agent to agent and capacity of the cylinder.

AutoFireX® Automatic Co2 DHP Fire Suppression Systems Advantages

How it works?

1
Detect

AutoFireX detects fires at the source using proprietary heat and flame detection tubing.

2
Activate

The AutoFireX system activates automatically, providing protection even when no one is around.

3
Suppress

AutoFireX systems suppress fires in seconds using clean agents that are safe for people, equipment, and the environment.